What is the Volume of Conductor Material Required in Underground DC System?


Underground DC System

When the DC electric power is transmitted from the power generating station to the consumer through the underground cables, then the electric power transmission system is called the underground DC system.

The underground DC transmission system is classified into three types −

  • Two-Wire DC System

  • Two-Wire DC System with Mid-Point Earthed

  • Three-Wire DC System

Conductor Material Required in Underground 2-Wire DC System

The underground two-wire DC system is shown in Figure-1. It has two conductors taken from the generator terminals.

Let,

  • 𝑉𝑚 = Maximum voltage between conductors

  • 𝑃 = Power to be transmitted

  • 𝑙 = Distance for which power is transmitted

The load current is given by,

$$\mathrm{\mathit{I_{\mathrm{1}}\mathrm{\, =\, }\frac{P}{V_{m}}}}$$

If 𝑎1 is the cross-sectional area of each conductor, then the resistance per conductor is,

$$\mathrm{\mathit{R_{\mathrm{1}}\mathrm{\, =\, }\rho \frac{l}{a_{\mathrm{1}}}}}$$

The total power losses in the system are given by,

$$\mathrm{\mathit{W\mathrm{\, =\, }\mathrm{2}I\mathrm{_{1}^{2}}\, R_{\mathrm{1}}\mathrm{\, =\, }\mathrm{2}\times \left ( \frac{P}{V_{m}} \right )^{\mathrm{2}}\times \left ( \frac{\rho \, l}{a_{\mathrm{1}}} \right )}}$$

$$\mathrm{\mathit{\Rightarrow W\mathrm{\, =\, }\frac{\mathrm{2}P^{\mathrm{2}\, }\rho l}{V_{m}^{\mathrm{2}}a_{\mathrm{1}}} }}$$

$$\mathrm{\therefore Area\: of\: cross\: section,\mathit{ \: a_{\mathrm{1}}\mathrm{\, =\, }\frac{\mathrm{2}P^{\mathrm{2}\, }\rho l}{WV_{m}^{\mathrm{2}}} }}$$

Thus, the volume of conductor material required in the underground 2-wire DC system, say K, is given by,

$$\mathrm{\mathit{ K\mathrm{\, =\, }\mathrm{2}a_{\mathrm{1}}l\mathrm{\, =\, }\mathrm{2}\times \left ( \frac{\mathrm{2}P^{\mathrm{2}\, }\rho l}{WV_{m}^{\mathrm{2}}} \right )\times l}}$$

$$\mathrm{\mathit{\therefore K\mathrm{\, =\, }\frac{\mathrm{4}P^{\mathrm{2}\, }\rho l^{\mathrm{2}}}{WV_{m}^{\mathrm{2}}}}\: \: \: \cdot \cdot \cdot \left ( 1 \right )} $$

Conductor Material Required in Underground 2-Wire DC System with Mid-Point Earthed

The circuit diagram of the underground 2-wire DC system with mid-point earthed is shown in Figure-2.

Let,

  • 𝑉𝑚 = Maximum voltage between conductors
  • 𝑃 = Power to be transmitted

Then, the load current is given by,

$$\mathrm{\mathit{I_{\mathrm{2}}\mathrm{\, =\, }\frac{P}{V_{m}}}}$$

If 𝑎2 is the area of cross-section of each conductor, then the resistance per conductor is,

$$\mathrm{\mathit{R_{\mathrm{2}}\mathrm{\, =\, }\rho \frac{l}{a_{\mathrm{2}}}}}$$

The total power losses in the system is given by,

$$\mathrm{\mathit{W\mathrm{\, =\, }\mathrm{2}I\mathrm{_{2}^{2}}\, R_{\mathrm{2}}\mathrm{\, =\, }\mathrm{2}\times \left ( \frac{P}{V_{m}} \right )^{\mathrm{2}}\times \left ( \frac{\rho \, l}{a_{\mathrm{2}}} \right )}}$$

$$\mathrm{\mathit{\Rightarrow W\mathrm{\, =\, }\frac{\mathrm{2}P^{\mathrm{2}\, }\rho l}{V_{m}^{\mathrm{2}}a_{\mathrm{2}}} }}$$

$$\mathrm{\therefore Area\: of\: cross\: section,\mathit{ \: a_{\mathrm{2}}\mathrm{\, =\, }\frac{\mathrm{2}P^{\mathrm{2}\, }\rho l}{WV_{m}^{\mathrm{2}}} }} $$

Therefore, the volume of conductor material required in the underground 2-wire DC system with mid-point earthed, say K1, is given by,

$$\mathrm{\mathit{ K_{\mathrm{1}}\mathrm{\, =\, }\mathrm{2}a_{\mathrm{2}}l\mathrm{\, =\, }\mathrm{2}\times \left ( \frac{\mathrm{2}P^{\mathrm{2}\, }\rho l}{WV_{m}^{\mathrm{2}}} \right )\times l}}$$

$$\mathrm{\mathit{\therefore K_{\mathrm{1}}\mathrm{\, =\, }\frac{\mathrm{4}P^{\mathrm{2}\, }\rho l^{\mathrm{2}}}{WV_{m}^{\mathrm{2}}}}\: \: \: \cdot \cdot \cdot \left ( 2 \right )}$$

Comparing equations (1) & (2), we get,

$$\mathrm{\mathit{\frac{K_{\mathrm{1}}}{K}\mathrm{\, =\, }\frac{\left ( \frac{\mathrm{4}P^{\mathrm{2}\, }\rho l^{\mathrm{2}}}{WV_{m}^{\mathrm{2}}} \right )}{\left (\frac{\mathrm{4}P^{\mathrm{2}\, }\rho l^{\mathrm{2}}}{WV_{m}^{\mathrm{2}}} \right )}}\mathrm{\, =\, }1}$$

$$\mathrm{\mathit{\therefore K_{\mathrm{1}}\mathrm{\, =\, }K}\: \: \: \cdot \cdot \cdot \left ( 3 \right )} $$

Hence, the volume of conductor material required in the underground 2-wire DC system with mid-point earthed is the same as that for underground 2-wire DC system.

Conductor Material Required in Underground Three-Wire DC System

The circuit diagram of an underground three-wire DC system is shown in Figure-3. In this system, the two outer line conductors are taken from the outer terminals of the generators and the neutral wire is taken from the mid-point. When the balanced load is connected to the system, the current in the neutral wire will be zero.

Let,

  • 𝑉𝑚 = Maximum voltage between outer conductors

  • 𝑃 = Power to be transmitted

Then, the load current in the system is given by,

$$\mathrm{\mathit{I_{\mathrm{3}}\mathrm{\, =\, }\frac{P}{V_{m}}}}$$

Also, if 𝑎3 is the area of cross-section of each conductor, then the resistance per conductor is,

$$\mathrm{\mathit{R_{\mathrm{3}}\mathrm{\, =\, }\rho \frac{l}{a_{\mathrm{3}}}}}$$

Hence, the total power losses in the system are given by,

$$\mathrm{\mathit{W\mathrm{\, =\, }\mathrm{2}I\mathrm{_{3}^{2}}\, R_{\mathrm{3}}\mathrm{\, =\, }\mathrm{2}\times \left ( \frac{P}{V_{m}} \right )^{\mathrm{2}}\times \left (\rho \frac{ \, l}{a_{\mathrm{3}}} \right )}}$$

$$\mathrm{\mathit{\Rightarrow W\mathrm{\, =\, }\frac{\mathrm{2}P^{\mathrm{2}\, }\rho l}{V_{m}^{\mathrm{2}}a_{\mathrm{3}}} }}$$

$$\mathrm{\therefore Area\: of\: cross\: section,\mathit{ \: a_{\mathrm{3}}\mathrm{\, =\, }\frac{\mathrm{2}P^{\mathrm{2}\, }\rho l}{WV_{m}^{\mathrm{2}}} }}$$

Assuming the area of cross-section of the neutral wire to be half of that of outer line wires.

Therefore, the volume of conductor material required in the underground three-wire DC system, say K2, is given by,

$$\mathrm{\mathit{ K_{\mathrm{2}}\mathrm{\, =\, }\mathrm{2.5}a_{\mathrm{3}}l\mathrm{\, =\, }\mathrm{2.5}\times \left ( \frac{\mathrm{2}P^{\mathrm{2}\, }\rho l}{WV_{m}^{\mathrm{2}}} \right )\times l}}$$

$$\mathrm{\mathit{\therefore K_{\mathrm{2}}\mathrm{\, =\, }\frac{\mathrm{5}P^{\mathrm{2}\, }\rho l^{\mathrm{2}}}{WV_{m}^{\mathrm{2}}}}\: \: \: \cdot \cdot \cdot \left ( 4 \right )}$$

Comparing equation (4) with (1), we get,

$$\mathrm{\mathit{ \frac{K_{\mathrm{2}}}{K}\mathrm{\, =\, }\frac{\left ( \frac{\mathrm{5}P^{\mathrm{2}\, }\rho l^{\mathrm{2}}}{WV_{m}^{\mathrm{2}}} \right )}{\left ( \frac{\mathrm{4}P^{\mathrm{2}\, }\rho l^{\mathrm{2}}}{WV_{m}^{\mathrm{2}}} \right )}}\mathrm{\, =\, }1.25}$$

$$\mathrm{\mathit{\therefore K_{\mathrm{2}}\mathrm{\, =\, }\mathrm{1.25}\times K}\: \: \: \cdot \cdot \cdot \left ( 5 \right )}$$

Hence, the volume of conductor material require in the underground three-wire DC system is 1.25 times that required for the underground 2-wire DC system.

Updated on: 25-Feb-2022

402 Views

Kickstart Your Career

Get certified by completing the course

Get Started
Advertisements